vacon • 100 Options
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
69
1310
Fieldbus
mapping error
Non-existing ID number is used for
mapping values to Fieldbus Process
Data Out.
Check parameters in Fieldbus
Data Mapping menu.
1311
Not possible to convert one or more
values for Fieldbus Process Data Out.
The value being mapped may
be of undefined type. Check
parameters in Fieldbus Data
Mapping menu.
1312
Overflow when mapping and converting
values for Fieldbus Process Data Out
(16-bit).
76 1076
Start prevented
Start command is active and was
blocked in order to prevent uninten-
tional rotation of the motor during the
first power-up.
Reset drive to restore the nor-
mal operation. The need of
restart depends on the parame-
ter settings.
77 1077
>5 connections
Maximum number of 5 simultaneous
active fieldbus or PC tool connections
supported by the application exceeded.
Remove excessive active con-
nections.
100 1100
Soft fill time-out
The Soft fill function in the PID control-
ler has timed out. The wanted process
value was not achieved within time.
Reason might be a pipe burst.
101 1101
Process
supervision fault
(PID1)
PID controller: Feedback value outside
of supervision limits (and the delay if
set).
Check settings.
105 1105
Process
supervision fault
(PID2)
PID controller: Feedback value outside
of supervision limits (and the delay if
set).
Check settings.
109
1109
Input pressure
supervision
Input pressure supervision signal has
gone below the alarm limit.
Check the process.
Check the parameters
Check the input pressure sen-
sor and connections.
1409
Input pressure supervision signal has
gone below the fault limit.
111
1315
Temperature
fault 1
At least one of the selected tempera-
ture input signals has reached the
alarm limit. Find the cause of temperature
raise.
Check the temperature sensor
and connections.
Check that the temperature
input is hard wired if no sensor
is connected.
See option board manual for
further information.
1316
At least one of the selected tempera-
ture input signals has reached the fault
limit.
112
1317
Temperature
fault 2
At least one of the selected tempera-
ture input signals has reached the fault
limit.
1318
At least one of the selected tempera-
ture input signals has reached the fault
limit.
113
1113
Pump running
time
In the Multipump system, 1 or more of
the pump runtime counters is above a
user-specified alarm limit.
Do the necessary maintenance
actions, reset the runtime
counter and reset the alarm.
See Pump running time coun-
ters.
1313
In the Multipump system, 1 or more of
the pump runtime counters is above a
user-specified Fault limit
Table 36. Fault codes and descriptions.
Fault
code
Fault
ID
Fault name Possible cause Remedy