vacon • 126 Solar pump application
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
10.6 Photovoltaic system dimensioning
The photovoltaic system has to be dimensioned in order to not exceed the values specified in the
tables below.
Table 56. VACON
®
100 X (208…240V 3AC 50/60Hz, up to 400V in VDC) DC-link input ratings
Enclosure
size
AC drive type DC supply [V]
Max. Recommended PV Array Power
[kW]
MM4
0007
234 … 400V
DC
No tolerance permissible,
0%
2.2
0008 3.0
0011 4.4
0012 6.0
MM5
0018 8.0
0024 11.0
0031 15.0
MM6
0048 22.0
0062 30.0
Table 57. VACON
®
100 X (380…480/500V 3AC 50/60Hz, up to 800V in VDC) DC-link input
ratings
Enclosure
size
AC drive type DC supply [V]
Max. Recommended PV Array Power
[kW]
MM4
0003
436 … 800V
DC
No tolerance permissible,
0%
2.2
0004 3.0
0005 4.4
0008 6.0
0009 8.0
0012 11.0
MM5
0016 15.0
0023 22.0
0031 30.0
MM6
0038 37.0
0046 44.0
0061 60.0
0072 74.0