vacon • 62 Commissioning
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
6.4 Maintenance
In normal conditions, the AC drive is maintenance-free. However, regular maintenance is recom-
mended to ensure trouble-free operation and longevity of the drive. We recommend the table below
is followed for maintenance intervals.
NOTE: Because of capacitor type (thin film capacitors), reforming of capacitors is not necessary.
Maintenance interval Maintenance action
Regularly and according to
general maintenance interval
Check tightening torques of terminals
6...24 months (depending on
environment)
Check input and output terminals and
control I/O terminals.
Check operation of cooling fan
Check the heatsink for dust and clean
if necessary
6...20 years Change main fan
10 years Replace the battery of the RTC.