4
vacon • 44 Power cabling
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Tightening torques of cable terminals:
Table 20. Tightening torques of terminals.
Enclosure
size
Type
Tightening torque
[Nm]/[lb-in.]
Power and motor
terminals
Tightening torque
[Nm]/[lb-in.]
EMC grounding
clamps
Tightening torque,
[Nm]/[lb-in.]
Grounding
terminals
[Nm] lb-in. [Nm] lb-in. [Nm] lb-in.
MM4
0007 2 - 0012 2
0003 4 - 0012 4
0003 5 - 0012 5
1.2—1.5 10.6—13.3 1.5 13.3 2.0 17.7
MM5
0018 2 - 0031 2
0016 4 - 0031 4
0016 5 - 0031 5
1.2—1.5 10.6—13.3 1.5 13.3 2.0 17.7
MM6
0048 2 - 0062 2
0038 4 - 0072 4
0038 5 - 0072 5
4—5 35.4—44.3 1.5 13.3 2.0 17.7
14
• Check the connection of the earth cable to the motor and the AC drive termi-
nals marked with .