Technical data vacon • 69
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
7
Directives
EMC 2004/108/EC
Low Voltage Directive 2006/95/EC
RoHS 2002/95/EC
WEEE 2012/19/EC
Standards
Immunity
EN61800-3 (2004), 1
st
and 2
nd
environment
Emissions
EN61800-3 (2004), Category C2
The drive can be modified for IT-networks.
THD EN61000-3-12 (see chapter 1.9)
Safety EN 61800-5-1
Production quality ISO 9001
Approvals
Functional Safety TÜV - Tested
Electrical Safety TÜV - Tested
EMC TÜV - Tested
USA, Canada cULus approval, file number E171278
Declaration of
Conformity
Korea KC mark
Australia
RCM Declaration of Conformity
Registration number E2204
Europe EC Declaration of Conformity
Protections
Undervoltage trip limit
Depends on supply voltage (0.8775*supply volt-
age):
Supply voltage 240 V: Trip limit 211 V
Supply voltage 400 V: Trip limit 351 V
Supply voltage 480 V: Trip limit 421 V
Overvoltage fault protec-
tion
Yes
Earth fault protection Yes
Mains supervision Yes
Motor phase supervision Yes
Overcurrent protection Yes
Unit overtemperature
protection
Yes
Motor overload protec-
tion
Yes. These devices provide motor overload protec-
tion at 105% of full load amperes.
Motor stall protection Yes
Motor underload protec-
tion
Yes
Short-circuit protection
of +24V and +10V refer-
ence voltages
Yes
Thermal motor protec-
tion
Yes (by PTC)
DC-link absolute maxi-
mum voltage
Supply voltage 240 V: absolute maximum 450V
DC
Supply voltage 400 V: 900V
DC
Table 33. VACON
®