Fault tracing vacon • 147
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
9
7 Saturation trip
Various causes:
- defective component
- brake resistor short-circuit or
overload
Cannot be reset from the
keypad.
Switch off power.
DO NOT RE-CONNECT
POWER!
Contact your local
distributor.
If this fault appears
simultaneously with Fault 1,
check motor cables and
motor.
8 System fault
- component failure
- faulty operation
Note exceptional fault data record.
Subcode in T.14:
S1 = Feedback of motor voltage
S2 = Reserved
S3 = Reserved
S4 = ASIC trip
S5 = Disturbance in VaconBus
S6 = Feedback of charging switch
S7 = Charging switch
S8 = No power to driver card
S9 = Power unit communication (TX)
S10 = Power unit communication (Trip)
S11 = Power unit comm. (Measurement)
S12 = Expander board (slot D or E)
S30-S48 = OPT-AF board (slot B)
Reset the fault and restart.
Should the fault re-occur,
contact your local distributor.
9 Undervoltage
DC-link voltage is under the voltage
limits defined in Table 9.
- most probable cause: too low a
supply voltage
- AC drive internal fault
Subcode in T.14:
S1 = DC-link too low during run
S2 = No data from power unit
S3 = Undervoltage control supervision
In case of temporary supply
voltage break reset the fault
and restart the AC drive.
Check the supply voltage. If it
is adequate, an internal fail-
ure has occurred.
Contact your local distributor.
10
Input line
supervision
Input line phase is missing.
Subcode in T.14:
S1 = Phase supervision diode supply
S2 = Phase supervision active front end
Check supply voltage, fuses
and cable.
12
Brake chopper
supervision
- no brake resistor installed
- brake resistor is broken
- brake chopper failure
Check brake resistor and
cabling.
If ok, the chopper is faulty.
Contact your local distribu-
tor.
13
Frequency
converter
undertemperature
Heatsink temperature is under –10 °C.
Table 60. Fault codes
Fault
code
Fault Possible cause Correcting measures

Table of Contents

Other manuals for Vacon NX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon NX and is the answer not in the manual?

Vacon NX Specifications

General IconGeneral
Product TypeAC Drive
Control MethodScalar Control
EnclosureIP00, IP21
CommunicationEthernet
SafetySTO (Safe Torque Off)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit
Ambient Temperature Range-10°C to +50°C (with derating above +40°C)
Cooling MethodAir-cooled, Liquid-cooled

Related product manuals