6
vacon • 76 Electrical cabling and connections
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
1)
Due to insufficient number of terminal bolt connections for required amount of cables, the cabinet must be
equipped with an external flexible cable connection block at both mains and motor ends if stiff cable type is
used.
Units with 6-pulse supply
Note that all other sizes have 3 input terminals except for size CH74, which has 9 input terminals.
Units with 12-pulse supply
12-pulse supply can be used with drives of sizes CH72 and CH74. The number of input terminals for
both is 6.
If 12-pulse supply is used, pay also attention to the fuse selection, see page 82 and page 83.
See the tightening torques of bolts in Table 40.
CH62/72
0590_5
0650_5
590
650
3*(3*150+70) ** 25—185 4/M12
CH62/72 0730_5 730 3*(3*150+70) ** 25—185 4/M12
CH63 0820_5 820 3*(3*185+95) ** **** 8/M12
CH63 0920_5 920 4*(3*185+95 ** **** 8/M12
CH63 1030_5 1030 4*(3*185+95) ** **** 8/M12
CH63 1150_5 1150 5*(3*185+95) ** *** 8/M12
CH64 1370_5 1370 5*(3*185+95) ** *** 8/M12
CH64 1640_5 1640 6*(3*185+95) ** *** 8/M12
CH64 2060_5 2060 7*(3*185+95) ** *** 8/M12
CH64 2300_5 2300 8*(3*185+95) ** *** 8/M12
CH74
1)
1370_5 1370 5*(3*185+95) ** *** 4/M12
CH74
1)
1640_5 1640 6*(3*185+95) ** *** 4/M12
CH74
1)
2060_5 2060 7*(3*185+95) ** *** 4/M12
CH74
1)
2300_5 2300 8*(3*185+95) ** *** 4/M12
Table 37. Motor cable sizes, 525—690 V
Chassis Type I
th
Motor cable
Cu [mm
2
]
Terminal cable size
Max. number of
cables/
Bolt size
Main terminal
[mm
2
], max
Earth terminal
[mm
2
]
CH61 0170_6 170 3*95+50 185 Cu/Al 25—95 2/M12
CH61 0208_6 208 3*150+70 185 Cu/Al 25—95 2/M12
CH61 0261_6 261 3*185+95 185 Cu/Al 2 25—95 2/M12
Table 36. Motor cable sizes, 400—500 V
Chassis Type I
th
Motor cable
Cu [mm
2
]
Terminal cable size
Max. number of
cables/
Bolt size
Main
terminal
[mm
2
], max.
Earth terminal
[mm
2
]

Table of Contents

Other manuals for Vacon NX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon NX and is the answer not in the manual?

Vacon NX Specifications

General IconGeneral
Product TypeAC Drive
Control MethodScalar Control
EnclosureIP00, IP21
CommunicationEthernet
SafetySTO (Safe Torque Off)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit
Ambient Temperature Range-10°C to +50°C (with derating above +40°C)
Cooling MethodAir-cooled, Liquid-cooled

Related product manuals