5. On the terminal page, you can see all the incoming messages in the selected COM port.
When the terminal page is open, normal communication between the display and the
sensor stops. In the autosend mode, the display stops processing the messages coming
through the selected COM port. In the poll mode, the display stops polling the sensor.
If the terminal page is open for long, the display gives an audible alarm. When you return
to the data page, some of the data fields are empty until there is enough processed data
again.
7.18 Configuring NET connection settings
You can change the current or default NET communication settings for the Ethernet
connection.
1. Enter Maintenance mode.
2. On the Advanced settings page, press NET.
Chapter 7 – Advanced settings in Maintenance mode
75