# Turn logging on, choices are FILE or TERM or BOTH or NONE
LOG BOTH
If you are starting the integrator from a terminal, set this to BOTH.
If you are starting the integrator automatically, set this to FILE. The log file is stored
in /usr/iris_data/log.
IRIS_IN 30726
IRIS_IN_DIR /usr/iris_data/tdwr/
These entries configure the characteristics of the input from IRIS to the Integrator.
IRIS_IN is the socket port that is used by IRIS to notify the Integrator when a new
product is sent. This must match the IRIS setup/output network device that has been
configured to send products from IRIS to the Integrator. The default port is 30726.
The IRIS_IN_DIR is the directory where IRIS sends products to the Integrator. This
must match the directory configured at the beginning of this section and the directory
configured in IRIS setup/output for the TDWR integrator. See Configuring IRIS Product
Outputs for TDWR (page 340).
IRIS_OUT cyclone 30725
IRIS_OUT_DIR /usr/iris_data/product/
These entries configure the characteristics of the output from the Integrator to IRIS.
IRIS_OUT is the nodename (cyclone) and socket port (30725) where IRIS will receive
the data. Usually this is the local workstation where the Integrator is running. The
socket port should match the IRIS_NETRCV environment variable for the network
receiver. This is set in the /usr/sigmet/config/profile.
The IRIS_OUT_DIR is the directory where TDWR products are sent. This must match
the directory configured for IRIS_PRODUCTS, typically /usr/iris_data/
product. This is set in the /usr/sigmet/config/profile.
IRIS_IN_TIME 120
This is the time in seconds, after which, an input is considered to be "stale". For
example, if the LLWAS stops sending data, the Integrator continues to use the old
LLWAS data for 120 seconds (in the example). After 120 seconds, the old LLWAS data is
not used to make new TDWR products.
IRIS Product and Display User Guide M211319EN-H