Door calendar
Door
locked
Select a calendar which should lock the door during the configured time. No card/pin will be
accepted during this time.
Door
locked
Select a calendar which should unlock the door. The door will be unlocked during the configured
time.
Door triggers
Trigger Description
Triggers that will
Momentarily Unlock
door
If the assigned trigger is activated, the door will unlock for a defined period, then lock
again.
Trigger that will lock
the door
If the assigned trigger is activated, the door will get locked. No card/PIN will be
accepted.
Trigger that will
unlock the door
If the assigned trigger is activated, the door will get unlocked. No card/PIN will be
needed to open the door.
Trigger that will set
the door to normal
If the assigned trigger is activated, the door will get back to normal operation. This is to
undo locking/unlocking of the door. A card/will be is needed to open the door.
Door Interlock
Door interlock is feature that prevents the remaining doors in an interlock group from opening if any one
door in the group is open.
The following are example of how this feature is used:
l In two-doors entry systems used in some banks and other buildings. Usually push buttons or
card readers are used to gain entrance, and red and green LEDs show if the door can be opened
or not.
l In ATM technical areas connecting ATM doors. Typically all the ATM doors in addition to the
door that gives access to the area would be interlocked.
To create a door lock:
1. Create a Door Group. See Editing a door on page278.
2. Set the Interlock attribute for the required doors in the group. See Editing a door on page278.
3. Configure a door output for door interlock operation. This output becomes active for all the doors
of the interlock group whenever a door belonging to the group is open, including the open door
itself.
This output could be connected, for example, to a red LED or light to indicate that the door could
not be opened, and if inverted could be connected to a green LED or light.
To configure an output for door interlock.
1. In Full Engineer mode, select Configuration > Hardware > X-BUS > Expanders.
2. In the Expander Configuration page, click the Change Type button for the required output.
3. Select Door as the output type.
4. Select the required door and Interlocked as the output type.
SPC4xxx/5xxx/6xxx – Installation & Configuration Manual Engineer programming via the browser
© Vanderbilt 2018 282 A6V10276959-d
11.2018

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vanderbilt SPCA210.100 and is the answer not in the manual?

Vanderbilt SPCA210.100 Specifications

General IconGeneral
BrandVanderbilt
ModelSPCA210.100
CategoryPower Supply
LanguageEnglish

Related product manuals