EasyManua.ls Logo

Vertiv Tech SmartCabinet2-E Series - Page 52

Default Icon
87 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SmartCabinet2-E Series Computer Room Solution Product User Manual
46 Chapter 3 Operation Settings
3) Setting
Click the Setting tab to enter the Set Signal page to display the setup signal for the selected device, as shown in
Figure 3-46.
Figure 3-46 Setting signal
Batch settings can be made for signals, and 16 signals can be set in maximum batch size at a time.
4) Alarm signal
Click the Alarm Signal tab to enter the alarm signal page to display the alarm signal of the selected device, as shown
in the figure 3-47.
Figure 3-47 Alarm signal
Batch settings can be made for the level of the alarm signal, and 16 signals can be set in maximum batch size at a
time.
2. UPS shutdown
In the home page of the MSC intelligent monitoring system, click the UPS shutdown menu on the left, and you can
see one sub-menu: Server shutdown.
Click the Server Shutdown submenu under the UPS Shutdown menu to pop up the Server Shutdown Settings page
as shown in the Figure 3-48.
Figure 3-48 Server Shutdown settings page
In the Server Shutdown settings page, users can add and remove server shutdown tasks.
The steps to add the server shutdown are as follows:

Table of Contents