Vertiv | NetSure™ 8200 Series -48 VDC Power System Installation Manual (IM582140000) | Rev. A
temperature can also be used for the rectifier battery charge temperature compensation feature, or the battery
charge temperature compensation feature can be programmed to use the average or highest value of all
battery temperature probes. The battery charge temperature compensation feature allows the controller to
automatically increase or decrease the output voltage of the system to maintain battery float current as battery
temperature decreases or increases, respectively. Battery life can be extended when an optimum charge
voltage to the battery with respect to temperature is maintained. A temperature probe set to monitor battery
temperature can also be used for the BTRM (Battery Thermal Runaway Management) feature. The BTRM
feature lowers output voltage when a high temperature condition exists to control against battery thermal
runaway.
The temperature sensor end of the probe contains a tab with a 5/16” clearance hole for mounting.
A temperature probe programmed to monitor battery temperature should be mounted on the negative post of
a battery cell to sense battery temperature. A temperature probe used for battery charge temperature
compensation and/or BTRM (Battery Thermal Runaway Management) should also be mounted on the negative
post of a battery cell. A temperature probe programmed to monitor ambient temperature should be mounted
in a convenient location, away from direct sources of heat or cold.