Chapter 5: Detailed description of parameters
142
P6.03 - P6.06 RESERVED
FOV selection the function of output
The FOV output range is 0-10 V or 0-20 mA. The relationship between the ranges of pulse
and analogue outputs and the corresponding functions is shown in the following table.
See description P8.38 and P8.39.
See description P8.40 and P8.41.
If the timing function (P8.42) is enabled, the output is ON
when the actual running time of the inverter reaches the set
time.
If the FIV input is greater than P9.46 (upper limit of the input
voltage FIV) or lower than the value P9.45 (lower limit of the
input voltage FIV), the output is ON.
If the inverter is in REVERSE mode, the output will be
switched on.
See description P8.28 and P8.29.
Module
temperature
reached
If the heat sink temperature (P7.07) reaches the set module
threshold (P8.47), the output is ON.
See description P8.36 and P8.37.
Frequency lower
limit reached
If the RUN frequency reaches the lower limit, the output is
ON. During the stop, the output is still on.
If a fault occurs in the inverter and the inverter will not
continue, an alarm signal will switch on.
Actual running
time reached
If the actual runtime exceeds P8.53, the output is ON.