EasyManua.ls Logo

Waters 600e - Page 61

Default Icon
162 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
36 Making Electrical Connections to the 600 Controller
Figure 3-5 PowerLine Controller IEEE-488 Connections
4. Repeat steps 2 and 3 for additional PowerLine components.
Note: The maximum total cable length between IEEE-488 devices is 65 feet (20
meters). The maximum recommended cable length between two IEEE-488 devices
is 13 feet (4 meters). Longer total cable lengths can cause intermittent IEEE-488
communication failures.
5. Ensure that all IEEE-488 cable screws are fastened finger-tight.
6. Set a unique IEEE-488 address between 2 and 29 for each PowerLine device
connected on the IEEE-488 bus (see Section 3.3.3, Setting IEEE-488 Addresses).
Note: Perform the correct IEEE-488 powerup sequence for the PowerLine system
as described in Section 3.3.4, Performing IEEE-488 Powerup Sequence.
Attaching a Waters 432 Detector to a PowerLine System
In the PowerLine mode, the 600 PowerLine Controller supports operation with a Waters
432 conductivity detector through an interface box. You must use the interface box to
communicate with the 432 detector over the IEEE-488 interface. When operating with the
Waters 432 conductivity detector, the 600 PowerLine Controller supports operation
directly over the IEEE-488 interface (as illustrated in Figure 3-5).
1. Connect the IEEE-488 cable (stackable connector for daisy-chaining additional
instruments) from the 600 controller to the IEEE-488 connector on the interface box
(Figure 3-6).

Table of Contents

Other manuals for Waters 600e

Related product manuals