Sequence control configuration
The function for the sequence control is to be configured for each
motor line
1. None - This motor line does not use sequence control
2. Open - This motor line must wait for a “result” before opening
3. Close - This motor line must wait for a “result” before closing
Sequence control configuration – motor line
1. Max. unexpected overcuret
This is not a sequence control paramter
2. Max. unexpected overcurrent (motor)
This is not a sequence control paramter
3. Sequential control type
This motor line must wait for a „result“ before opening.
4. Sequential control position limit
the max position the motor line is allowed to have without the
„result“ is being fulfilled.
For MotorLink
®
motor lines stepless variable.
For ±24 Volt motor lines 0 or 100%
1. Sequential control with
Select the object the motor line is to wait upon.
Choose among another motor line, KNX-, BACnet-, local input or
delay timer.
1. Sequential control with
Upon which Motor line, KNX-, BACnet- or local input must the
motor line wait.
2. Sequential control with no.
Upon which Motor line, KNX-, BACnet- or local input must the
motor line wait.
3. Sequential control invert
No: waits for a close signal (active input )
Yes: waits for a open signal (inactive input)
4. Sequential control max. wait time
set the max wait time the motor line should wait, e.g. 60sec. the
motor line will then e.g. opens after 60 seconds even when the
input condition is not fulfilled. Values between 0 and 64,000
seconds are valid, both for comfort and smoke ventilation. When
set to 0 the motor line waites for ever.
1. Sequential control with
Delay timer
The motor line is set to wait for a certain period of time ‘Sequential
control max. wait time’. When the wait time has elapsed the motor
line will then move.