55
Smoke zones
They can be operated in ‘Alarm’ or ‘Reset’
Example
Manual operation of a motor line
- If ’All’ is selected all the motors are operated simultaneously.
- If a motor line number is selected only the selected motor line is operated.
Motor line - overview
One motor line is selected
Manual operation on the
touch screen
17 Configuration missing main menu
If any components, motor lines, motor groups or smoke zones are not configured they are listed here.
If you are logged into access level 3 it is also possible to configure from this menu.
18 Hardware error main menu
If there are any hardware error in a section, they will be displayed here.
E.g. if the motor lines are not configured, the main supply is cut of, the back-up batteries are not connected, the type of weather
station is not selected etc.
If you are logged into access level 3 it is also possible to configure from this menu.
18.1 Error on the Power supply
Mains power failure will trigger an error on the “Power supply”. The first 10 minutes (parameter setting) after the failure has been
detected, no error is indicated neither on the panel, the display nor in the break glass units.
The following 20 minutes the error will be indicated as a warning meaning the green LED on the break glass units will flash, on the
WSA-5MC module the green LED is still on and the yellow LED is turned off. 30 minutes after the mains power failure has been
detected all the green LED will turn off and the all the yellow LEDs in the smoke ventilation panel and the break glass units will lit
continuously.
Furthermore, non connected, wrong connected or ”dead” batteries can trigger an error on the ”Power supply”.
Error on the power supply
Error on the Battery status

Table of Contents

Other manuals for Window Master FlexiSmoke WSC 520

Related product manuals