Manual 26166V1 MicroNet Simplex & MicroNet Plus
Woodward 100
8.5—32 Channel Discrete Output Module
Module Obsolete. See Volume 3, Section 4 for information.
8.6—64 Channel Discrete Output Module
8.6.1—Module Description
Figure 8-16. Discrete Output Module
The MicroNet control can provide discrete outputs to the prime mover from field wiring. Each of this type
Discrete Output (DO) module can individually control 64 outputs according to commands from the CPU
module. These modules have no potentiometers and require no calibration. A module may be replaced
with another module of the same part number without any adjustment. There are several different FTM
I/O configurations for the 64Ch DO Module. The module can be connected to two 32Ch Relay Module,
four 16Ch Relay Modules, or a combination of the two types (see Chapter 13 for additional information on
the relay modules).
Table 8-5. Module Specification
Number of channels: 64
Update time: 5 ms
Output Type: Open drain drivers, intended for use with Woodward relay interface modules.
Fault Detection Read back: Output channel status, relay status is not available
System Faults: Outputs are turned off if communications with the CPU is lost.
For the 16Ch Relay Module, and the 32Ch Relay Module output specifications, see Chapter 13.