Manual 26166V1 MicroNet Simplex & MicroNet Plus
Woodward 113
When configuring the AI Combo block in GAP, set Conf. input field to 1
for all inputs working in 4-20mA current mode. This will allow the block
to use the module factory calibration values for inputs that were
calibrated with 200 ohm internal resistors on the 24/8 Analog Module.
When configuring the AI Combo block in GAP, set Conf. input field to 2
for all 4-20 mA inputs when used with the Dataforth current input plug-
in module. This will allow the block to use the module factory voltage
calibration values with a gain factor for a 200 ohm external resistor on
the Dataforth FTM.
Input type configuration is factory set for backward compatible part
numbers.
For modules with GAP selectable inputs, when changing the Conf.
input field to a new value an application save and application restart is
required before the module can be used. This save and restart allows
the hardware and software to be properly initialized together.
Figure 9-8. Analog Input Wiring for a 24/8 Analog FTM
Released