EasyManua.ls Logo

Woodward MicroNet Simplex - Figure 4-10. Outline Drawing of Micronet 6-Slot I;O

Woodward MicroNet Simplex
130 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Manual 26166V1 MicroNet Simplex & MicroNet Plus
Woodward 36
From a module connector standpoint, any I/O module can be installed in any of the slots designated for
I/O modules. However, when the application software is designed, each module will be assigned to a
specific slot and thereafter, the software will expect that specific I/O module to always be in its designated
slot.
Notes:
Add ~2” (~5 cm) to the depth dimension to account for the cable saddles that are not shown on the
outline drawing below.
The PE ground connection point is located underneath the left side of the chassis.
To ensure compliance with the EMC certification, all chassis mounting screws (#8-32 M4) should be
installed to properly ground the chassis to the mounting plate.
For proper airflow, the installation should allow a 3” (8 cm) air gap above and below the chassis.
Figure 4-10. Outline Drawing of MicroNet 6-Slot I/O
Released

Table of Contents

Related product manuals