6.3.11—Troubleshooting and Tuning
The MicroNet CPU module runs off-line and on-line diagnostics that display troubleshooting messages
through the debug Service Port and AppManager. Off-line diagnostics run automatically on power-up and
when the Reset switch is asserted. On-line diagnostics run during normal Control System operation when
the GAP application is active. More information on diagnostics tests, subsequent LED flash codes, and
serial port messages is contained in the VxWorks manual.
Table 6-9. CPU Fault LED Flash Codes
Failure Flash Code
RAM Test Failure 1, 4
Real Time Clock Test Failure 2, 2
Floating Point Unit Test Failure 2, 3
Flash Test Failure 2, 4
HD1 Flash Test Failure 2, 5
I2C Bus Test Failure 2, 6
Module Installed in wrong slot 2, 7
Main Chassis CPU switch must be set to 0 3,5
Remote RTN Rate Group 5 Slip 3, 7
Remote RTN Rate Group 10 Slip 3, 8
Remote RTN Rate Group 20 Slip 3, 9
Remote RTN Rate Group 40 Slip 3, 10
Remote RTN Rate Group 80 Slip 3, 11
Remote RTN Rate Group 160 Slip 3, 12
Remote RTN Chassis Switch Invalid 4, 5
Backup Remote RTN Chassis Switch different
from Primary Remote RTN
4, 6
This module does not support the CAN port(s) 4, 7