Manual 26166V1 MicroNet Simplex & MicroNet Plus
Woodward 37
4.3.2—Installation
Figure 4-11 shows the mounting template and fasteners to bulkhead mount the chassis. Rack mounting is
not recommended.
Figure 4-11. Mounting Template of MicroNet 6-Slot I/O Chassis
4.4—Simplex 12-Slot I/O (Input/Output)
4.4.1—Description
This chassis contains twelve slots for CPU and I/O (input/output) modules. Normally, this allows one CPU
module and eleven I/O modules. In addition to the 12 CPU – I/O slots, two power supply positions are
provided, which allows for redundant power input. Each power supply module occupies three slots of
chassis space. When counting power supply and I/O slots, the total width of the chassis is 18 slots wide.
If a power supply or I/O module slot is not occupied, it must be filled with a blanking plate (3799-301) to
maintain proper cooling flow through the chassis.