Manual 26166V1 MicroNet Simplex & MicroNet Plus
Woodward 117
Input Amplitude: 0-24Vpk,
Input Impedance: 2000
12mA short circuit current
Eddy ratings
Input Frequency Range: 1 Hz to 25 KHz
Input Amplitude: 0-24Vpk,
Input Impedance: 2000
12mA short circuit current
Common characteristics
Isolation Voltage: 500Vrms to earth ground and control common, no galvanic isolation
between channels
Resolution: 16 bits
0.0015% of range per LSB
Speed Accuracy (max):
P/N5466-1105 0.01% over temperature range
P/N5466-1115 0.03% over temperature range
Temperature drift: 1 ppm/ °C
Derivative Accuracy (max): 0.10% of range (p-p)
Speed Filter: 5-10,000 ms (2 real poles)
Derivative Filter: 5-10,000 ms (1 pole + speed filter)
Acceleration Limit: 1-10,000 percent/second
Operating Temperature: –15 to +65 °C
Speed probe supply current: 320mA
(total for all 4 channels)
Table 9-5. Analog Input Ratings
Number of channels: 12
Update time: 5 ms
Input range: 0-25 mA or 0-5 V; set in GAP application
Isolation: 500 Vrms galvanic isolation to earth ground and control common, no
galvanic isolation between channels
60 dB CMRR
200 Vdc common mode rejection voltage;
Input imp. (4-20 mA): 200 ohms
Anti-aliasing filter: 2 poles at 10 ms (CH01-10)
2 poles at 5ms (CH11-12)
Resolution: 16 bits
Accuracy: Software calibrated to 0.1%, over 0-25 mA or 0-5Vdc full scale
Temp drift: 275 ppm/C, maximum
Fuse: 100 mA fuse per channel located at FTM
Time stamping: 5 ms resolution on low event and latch, and high event and latch
Released