EasyManua.ls Logo

Woodward MicroNet Simplex - 9.28 24;8 Analog Smart Plus Module

Woodward MicroNet Simplex
130 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Manual 26166V1 MicroNet Simplex & MicroNet Plus
Woodward 111
Table 9-3. Module Specification
Analog Input Ratings
Number of channels: 24
Update time: 5 ms
Input range: 0-25 mA or 0-5 V; software and hardware selectable
Isolation:
500 Vrms galvanic isolation to earth ground and control
common, no galvanic isolation between channels
60 dB CMRR
200 Vdc common mode rejection voltage
Input imp. (4-20 mA): 200 ohms
Anti-aliasing filter:
2 poles at 10 ms (CH01-22)
2 poles at 5ms (CH23-24)
Resolution: 16 bits
Accuracy: Software calibrated to 0.1%, over 0-25 mA full scale
Temp drift: 275 ppm/C, maximum
Fuse: 100 mA fuse per channel located at FTM
Time stamping: 5 ms resolution on low event and latch, and high event and latch
Table 9-2. 4–20 mA Output Ratings
Number of channels: 8
Update time: 5 ms
Output Driver: linear
Filter: 1 pole at 1ms plus 1pole at 0.25ms
Current output: 4–20 mA
Current output range: 0-25 mA
Isolation: 500 Vrms galvanic isolation to earth ground and control
common, no galvanic isolation between channels
Max load resistance: 600 ohms (load + wire resistance)
Resolution: 14 bits
Accuracy: Software calibrated to 0.2% of 0-25 mA full scale
Temperature drift: 125 ppm/C, maximum
Source read back isolation: 60 dB CMRR, 200 Vdc common mode voltage rejection
Read back Resolution
Source: 12 bits
Return: 8 bits
Read back Accuracy
Source: 0.5% of 0-25 mA full scale
Return: 1% of 0-25 mA full scale
Read back temp drift: 400 ppm/C, maximum
Note: Item 5466-5025 (pending release in Q2 2016) must be used with Coder Version 5.08 or later.
Coder 4.06 compatible versions:
Item 5466-5026 is backward compatible with P/N 5466-332
Item 5466-5027 is backward compatible with P/N 5466-425
Note: Item 5466-5026 may be used in place of the 5466-315 if it is acceptable to have 5mS Anti-aliasing
filter on A/I channels 23/24. (vs 10mS anti-aliasing filter). Please consult application engineering.
Note: AI and AO readback accuracy may be affected if the control is placed in a high electrical noise
environment.
Released

Table of Contents

Related product manuals