5 HIGH SPEED COUNTER (HSC)
This chapter will introduce high speed counter’s functions, including high speed count model,
wiring method, read/write HSC value, reset etc.
Instructions List for HSC
Instruction
name
Function
Instruction
Chapter
HSC read/write
DMOV
HSC read
5-6-1
DMOV
HSC write
5-6-2
CNT
No 24-segments single
phase
5-7-1
CNT_AB
No 24-segments AB phase
5-7-2
CNT
24-segments single phase
5-7-3
CNT_AB
24-segments AB phase
5-7-4
RST
HSC reset
5-8
5-1Functions Summary
XD, XL series PLC has HSC (High Speed Counter) function which will not affect by the
scanning cycle. Via choosing different counter, test the high speed input signals with detect
sensors and rotary encoders. The highest testing frequency can reach 80 KHz.
Note:
(1) The high-speed counting input of XD/XL series PLC can only receive collector open-
circuit signal (OC), but can not receive differential signal, so it is necessary to select the
encoder of collector open-circuit signal (OC).
(2) When the counting frequency is higher than 25Hz, please select a high-speed counter.
(3) The XD1/XL1 series does not support high-speed counting.