EasyManua.ls Logo

Xinje XD5 - Advanced Mode

Xinje XD5
389 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
287
Over target value times in auto-tuning end transition stage when limiting the overshoot
[S3+15]
This parameter is valid only when [S3+13] is 1;
If entering into PID control directly after auto tune, small range of overshoot may occur. It is
good to prevent the overshoot if increasing this parameter properly. But it will cause response
lag if this value is too large. The default value is 15 times. The recommended range is from 5
to 20.
7-5Advanced Mode
Users can set some parameters in advanced mode in order to get better PID control effect.
Enter into the advanced mode, please set [S3+2] bit 15 to be 1, or set it in the XDP Pro
software.
Input Filter constant [S3+8]
It will smooth the sampling value. The default value is 0%, which means no filter.
Differential Gain[S3+9]
The low pass filtering process will relax the sharp change of the output value. The default
value is 50%; the relaxing effect will be more obviously if increasing this value. Users do not
need to change it.
Upper-limit and lower-limit value [S3+10], [S3+11]
Users can choose the analog output range via setting this value.
Default value: lower-limit output =0
Upper-limit =4095
t
100
96
88
66
Current system value
Current target 3
Current target 2
Current target 1
Target value

Table of Contents

Related product manuals