348
10-4-2. Timing Interruption
Y0
FEND
I4010
INC D0
IRET
X0
SM0
XD, XL series timing interruption:
Interruption
number
Interruption
ban
instruction
Interruption
number
Interruption
ban
instruction
Explanation
I40**
SM070
I50**
SM080
** means the timing
interruption time, the range
is
1~99, the unit is ms.
I41**
SM071
I51**
SM081
I42**
SM072
I52**
SM082
I43**
SM073
I53**
SM083
I44**
SM074
I54**
SM084
I45**
SM075
I55**
SM085
I46**
SM076
I56**
SM086
I47**
SM077
I57**
SM087
Function and Action
Under the circumstance that the main program execution cycle is very long, when you
have to handle with special program or execute specific program every once in a while
when program is scanning in sequence control, the timing interruption is very useful. It is
not affected by PLC scan cycle and executes timing interruption subroutine every N ms.
Timing interruption is open status in default, just like other interruption subroutines, it
should be written behind the main program, starts with I40xx, ends with IRET.
There are 20 channels of timing interruptions, representation: I40**~I59**(‘**’means
interruption time; Unit is ms. E.g: I4010 means executing once the first timing
interruption per 10ms.
Interruption No