Xinje XD5 - BLOCK Related Instructions; Stop Running the BLOCK [SBSTOP]

Xinje XD5
389 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
322
BLOCK is not recommended to put in the STL, because if one STL ends, while the BLOCK
doesn’t end, then big problem will happen.
NO×
YES
SM0
SBLOCK
FROM K0 K1 K5 D100
WAIT K1 K50
STL S0
SBLOCKE
M100
( )
STLE
Y0
PLSR HD0 HD100 K1 Y0
S0
SBLOCK
FROM K0 K1 K5 D100
WAIT K1 K50
STL S0
SBLOCKE
M100
( )
STLE
Y0
PLSR HD0 HD100 K1 Y0
Label Kind type cannot be used in the block
Sign P, I cannot be used in block. Even they can be added in block, but they do not work in
fact.
9-6BLOCK related instructions
9-6-1Instruction explanation
stop running the BLOCK [SBSTOP]
Summarization
Stop the instructions running in the block
[SBSTOP]
16 bits
SBSTOP
32 bits
-
Condition
NO,NC coil and pulse edge
Suitable
types
XD, XL
Hardware
Software
V3.2
Operand
Operand
Function
Type
S1
The number of the BLOCK
16bits, BIN
S2
The mode to stop the BLOCK
16bits, BIN
Suitable component
*Note: D includes D, HD; TD includes TD, HTD; CD includes CD, HCD, HSCD, HSD;
DM includes DM, DHM; DS includes DS, DHS.
Word
Operand
Register
Constant
Module
D
*
FD
TD
*
CD
*
DX
DY
DM
*
DS
*
K /H
ID
QD
S1
S2