270
SD151
X-Net communication
result
0: correct
1: communication timeout
2: memory error
3: receive CRC error
SD152
Free communication
sending result
0: correct
410: free communication buffer
overflow
SD153
Free communication
receiving result
0: correct
410: send data length overflow
411: receive data short
412: receive data long
413: receive error
414: receive timeout
415: no start symbol
416: no end symbol
SD154
free communication
receiving data number
Count as byte, not include start
symbol and end symbol
……
SD159
Port 2
SD160
Modbus read and write
instruction execution result
0: correct
100: receive error
101: receive timeout
180: CRC error
181: LRC error
182: station number error
183: send buffer overflow
400: function code error
401: address error
402: length error
403: data error
404: slave station busy
405: memory error (erase FLASH)
SD161
X-Net communication
result
0: correct
1: communication timeout
2: memory error
3: receive CRC error
SD162
Free communication
sending result
0: correct
410: free communication buffer
overflow
SD163
Free communication
receiving result
0: correct
410: send data length overflow
411: receive data short
412: receive data long
413: receive error
414: receive timeout
415: no start symbol
416: no end symbol
SD164
free communication
receiving data number
Count as byte, not include start
symbol and end symbol
……
SD169
Port 3
SD170~SD179
Port 4
SD180~SD189
Port 5
SD190~SD199