Parameter Details
12
12.7 F: Options
YASKAWA SIEPC71061753C GA500 Technical Manual 617
4 : RUN Reverse
F6-55: DeviceNet Baud Rate Monitor
No.
(Hex.)
Name Description
Default
(Range)
F6-55
(03C6)
DeviceNet Baud Rate
Monitor
Sets the function to see the actual DeviceNet communications speed using the keypad. This
parameter functions as a monitor only.
0
(0 - 2)
0 : 125 kbps
1 : 250 kbps
2 : 500 kbps
F6-56: DeviceNet Speed Scaling
No.
(Hex.)
Name Description
Default
(Range)
F6-56
(03D7)
DeviceNet Speed Scaling
Sets the speed scale for DeviceNet communication.
0
(-15 - +15)
F6-57: DeviceNet Current Scaling
No.
(Hex.)
Name Description
Default
(Range)
F6-57
(03D8)
DeviceNet Current Scaling
Sets the current scale of the DeviceNet communication master.
0
(-15 - +15)
F6-58: DeviceNet Torque Scaling
No.
(Hex.)
Name Description
Default
(Range)
F6-58
(03D9)
DeviceNet Torque Scaling
Sets the torque scale of the DeviceNet communication master.
0
(-15 - +15)
F6-59: DeviceNet Power Scaling
No.
(Hex.)
Name Description
Default
(Range)
F6-59
(03DA)
DeviceNet Power Scaling
Sets the power scale of the DeviceNet communication master.
0
(-15 - +15)
F6-60: DeviceNet Voltage Scaling
No.
(Hex.)
Name Description
Default
(Range)
F6-60
(03DB)
DeviceNet Voltage Scaling
Sets the voltage scale of the DeviceNet communication master.
0
(-15 - +15)
F6-61: DeviceNet Time Scaling
No.
(Hex.)
Name Description
Default
(Range)
F6-61
(03DC)
DeviceNet Time Scaling
Sets the time scale of the DeviceNet communication master.
0
(-15 - +15)
F6-62: DeviceNet Heartbeat Interval
No.
(Hex.)
Name Description
Default
(Range)
F6-62
(03DD)
DeviceNet Heartbeat
Interval
Sets the heartbeat for DeviceNet communication. Set this parameter to 0 to disable the heartbeat
function.
0
(0 - 10)
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA CIPR-GA50C series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA CIPR-GA50C series and is the answer not in the manual?

YASKAWA CIPR-GA50C series Specifications

General IconGeneral
BrandYASKAWA
ModelCIPR-GA50C series
CategoryController
LanguageEnglish

Related product manuals