2.5 E: Motor Parameters
162 YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
n E4-06: Motor 2 Leakage Inductance
Sets the voltage drop due to motor leakage inductance as a percentage of rated voltage of motor 2.
n
E4-07: Motor 2 Motor Iron-Core Saturation Coefficient 1
Sets the motor 2 iron saturation coefficient at 50% of magnetic flux. This value is automatically set during Rotational
Auto-Tuning. Adjust this parameter when operating in the constant output range.
n
E4-08: Motor 2 Motor Iron-Core Saturation Coefficient 2
Sets the motor 2 iron saturation coefficient at 75% of magnetic flux. This value is automatically set during Rotational
Auto-Tuning. Adjust this parameter when operating in the constant output range.
n
E4-09: Motor 2 Mechanical Loss
Sets the motor mechanical loss as a percentage of motor rated power (kW).
Although E4-09 rarely needs to be changed, adjustment may be necessary in the following circumstances:
• When there is a large amount of torque loss due to motor bearing friction.
• When there is a large amount of torque loss in a fan or pump application.
n
E4-10: Motor 2 Iron Loss
Sets the motor 2 iron loss in watts.
n
E4-11: Motor 2 Rated Power
Sets the motor 2 rated power. If Auto-Tuning completes successfully, the value entered to T1-02 will automatically be
saved to E4-11.
No.
<1> For details on the default settings, refer to Defaults by Drive Model Selection (o2-04) on page 87.
Name Setting Range Default
E4-06 Motor 2 Leakage Inductance 0.0 to 40.0% Determined by o2-04 <1>
No. Name Setting Range Default
E4-07
Motor 2 Motor Iron-Core Saturation Coefficient
1
0.00 to 0.50 0.50
No. Name Setting Range Default
E4-08
Motor 2 Motor Iron-Core Saturation Coefficient
2
[E4-07] to 0.75 0.75
No. Name Setting Range Default
E4-09 Motor 2 Mechanical Loss 0.0 to 10.0% 0.0%
No.
<1> For details on the default settings, refer to Defaults by Drive Model Selection (o2-04) on page 87.
Name Setting Range Default
E4-10 Motor 2 Iron Loss 0 to 65535 W Determined by o2-04 <1>
No.
<1> For details on the default settings, refer to Defaults by Drive Model Selection (o2-04) on page 87.
Name Setting Range Default
E4-11 Motor 2 Rated Power 0 to 65000 kW Determined by o2-04 <1>