EasyManua.ls Logo

YASKAWA FSDrive-MV1000 - Page 196

YASKAWA FSDrive-MV1000
241 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.7 H: Terminal Functions
196 YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
Setting 5: Accel/decel time gain
Adjusts the gain level for the acceleration and deceleration times set in parameters C1-01 through C1-08.
The acceleration time used by the drive is calculated by multiplying this gain level by C1- as follows:
C1- × Accel/decel time gain = Drive accel/decel time
Figure 2. 66
Figure 2.66 Accel/Decel Time Gain with Analog Input Terminal
Setting 6: DC Injection Braking current
The current level used for DC Injection Braking. Set as a percentage of the maximum output current using.
When setting the bias by parameter, however, make the setting as a percentage of the motor rated current.
Note also that the DC injection braking current is limited by the motor rated current value.
Figure 2. 67
Figure 2.67 DC Injection Braking Current Using an Analog Input Terminal
Setting 7: Torque Detection level
Using this setting, the overtorque/undertorque detection level for Torque Detection Selection 1 (L6-01) can be set by an
analog input. The analog input will replace the level set for Torque Detection Level 1 (L6-02). An analog input of 100%
(10 V) will set a torque detection level equal to 100% drive rated current / motor rated torque. Adjust the analog input
gain if higher detection level settings are required. Refer to L6: Torque Detection on page 213 for details.
Setting 8: Stall Prevention level
This setting allows an analog input signal to adjust the Stall Prevention level. Figure 2.68 shows the setting
characteristics. The drive will use either the Stall Prevention level set in L3-06 or the level coming from the analog input
terminal that has been selected, whichever value is lower.
Figure 2. 68
Figure 2.68 Stall Prevention During Run Using an Analog Input Terminal
Setting 9: Output frequency lower limit level
The user can adjust the lower limit of the output frequency using an analog input signal.
Setting B: PID feedback
An input set for this function supplies the PID feedback value. This setting requires PID operation to be enabled in b5-01.
Refer to PID Feedback Input Methods on page 116.
100%
50%
0 5 V 10 V
1
V2
V
20%
10%
Acceleration/deceleration gain from 1 to 10 V
(10 V)
Input Voltage (V)
×
10 (%)
=
      
common_TMonly
Drive Rated
Current
0
100%
10 V
DC Injection Braking Current Level
common_TMonly
Stall Prevention Level during Run
30%
100%
Analog Input Value of Input Terminal
30% 100%0
common_TMonly
MV1000ParameterGuide_E_conditional.book 196 ペー 01年1月1日 日 午後8時18分

Table of Contents

Other manuals for YASKAWA FSDrive-MV1000

Related product manuals