1.3  Parameter Table
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide  31
b5-39
(1FFH)
PID Setpoint 
Display Digits
0: No decimal places
1: One decimal place
2: Two decimal places
3: Three decimal places
Default:
<5>
Min: 0
Max: 3
125
b5-40
(17FH)
Frequency 
Reference Monitor 
Content during PID
0: Display the frequency reference (U1-01) after PID compensation has been 
added.
1: Display the frequency reference (U1-01) before PID compensation has 
been added.
Default: 0
Min: 0
Max: 1
125
b6: Dwell Function
b6-01
(1B6H)
Dwell Reference at 
Start
Parameters b6-01 and b6-02 set the frequency to hold and the time to 
maintain that frequency at start.
Parameters b6-03 and b6-04 set the frequency to hold and the time to 
maintain that frequency at stop.
Default:
<10>
Min: 0.0 Hz
Max: 120.0 Hz 
<20>
126
b6-02
(1B7H)
Dwell Time at Start
Default: 0.0 s
Min: 0.0 s
Max: 10.0 s
126
b6-03
(1B8H)
Dwell Reference at 
Stop
Default:
<10>
Min: 0.0 Hz
Max: 120.0 Hz 
<20>
126
b6-04
(1B9H)
Dwell Time at Stop
Default: 0.0 s
Min: 0.0 s
Max: 10.0 s
126
b7: Droop Control
b7-01
(1CAH)
Droop Control Gain
Sets the speed reduction gain applied at a torque reference of 100%. Set as a 
percentage of motor base speed.
Default: 0.0%
Min: 0.0%
Max: 100.0%
127
b7-02
(1CBH)
Droop Control 
Delay Time
Used to adjust the responsiveness of Droop Control.
Default: 0.05 s
Min: 0.03 s
Max: 2.00 s
127
b7-03
(17EH)
Droop Control Limit 
Selection
0: Disabled
1: Enabled
Default: 1
Min: 0
Max: 1
127
<5> Default setting is determined by b5-20, PID Setpoint Scaling.
<6> Default setting is determined by o2-04, Drive Model Selection.
<8> Parameter value changes automatically if E2-11 is manually changed or changed by Auto-Tuning.
<10> Default setting is determined by A1-02, Control Method Selection.
<11> Settings 2 and 3 are not available when using CLV.
<20> Range upper limit is determined by E1-04, Maximum Output Frequency, and d2-01, Frequency Reference Upper Limit.
<36> Default setting is determined by o1-03, Digital Operator Display Selection.
No.
(Addr.)
Name Description Setting  Page
b6-01
b6-03
b6-02 b6-04
RUN 
command
Time
Output 
frequency
ON
OFF
CLV
V/f
OLV
CLV
V/f
OLV