1.3 Parameter Table
30 YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
b5-12
(1B0H)
PID Feedback Loss
Detection Selection
0: No fault. Contact output only.
1: Fault detection. Alarm output, drive continues operation.
2: Fault detection. Fault output, drive output is shut off.
3: No fault. Contact output only. No fault detection when PID control is
disabled.
4: Fault detection. Alarm is triggered and drive continues to run. Fault
detection even when PID is disabled.
5: Fault detection. Drive output shuts off. No fault detection when PID
control is disabled.
Default: 0
Min: 0
Max: 5
122
b5-13
(1B1H)
PID Feedback Loss
Detection Level
Sets the PID feedback loss detection level as a percentage of the maximum
output frequency.
Default: 0%
Min: 0%
Max: 100%
122
b5-14
(1B2H)
PID Feedback Loss
Detection Time
Sets a delay time for PID feedback loss.
Default: 1.0 s
Min: 0.0 s
Max: 25.5 s
122
b5-15
(1B3H)
PID Sleep Function
Start Level
Sets the frequency level that triggers the sleep function.
Default:
<10>
Min: 0.0 Hz
Max: 120.0 Hz
123
b5-16
(1B4H)
PID Sleep Delay
Time
Sets a delay time before the sleep function is triggered.
Default: 0.0 s
Min: 0.0 s
Max: 25.5 s
123
b5-17
(1B5H)
PID Accel/Decel
Time
Sets the acceleration and deceleration time to PID setpoint.
Default: 0.0 s
Min: 0.0 s
Max: 6000.0 s
123
b5-18
(1DCH)
PID Setpoint
Selection
0: Disabled
1: Enabled
Default: 0
Min: 0
Max: 1
124
b5-19
(1DDH)
PID Setpoint Value
Sets the PID target value when b5-18 = 1. Set as a percentage of the
maximum output frequency.
Default: 0.00%
Min: 0.00%
Max: 100.00%
124
b5-20
(1E2H)
PID Setpoint
Scaling
0: 0.01Hz units
1: 0.01% units (100% = max output frequency)
2: r/min (number of motor poles must entered)
3: User-set (set scaling to b5-38 and b5-39)
Default: 1
Min: 0
Max: 3
124
b5-34
(19FH)
PID Output Lower
Limit
Sets the minimum output possible from the PID controller as a percentage of
the maximum output frequency.
Default: 0.00%
Min: -100.0%
Max: 100.0%
124
b5-35
(1A0H)
PID Input Limit
Limits the PID control input (deviation signal) as a percentage of the
maximum output frequency. Acts as a bipolar limit.
Default: 1000.0%
Min: 0%
Max: 1000.0%
124
b5-36
(1A1H)
PID Feedback High
Detection Level
Sets the PID feedback high detection level as a percentage of the maximum
output frequency.
Default: 100%
Min: 0%
Max: 100%
122
b5-37
(1A2H)
PID Feedback High
Detection Time
Sets the PID feedback high level detection delay time.
Default: 1.0 s
Min: 0.0 s
Max: 25.5 s
123
b5-38
(1FEH)
PID Setpoint User
Display
Sets the display value of U5-01 and U5-04 when the maximum frequency is
output.
Default:
<5>
Min: 1
Max: 60000
125
No.
(Addr.)
Name Description Setting Page
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
MV1000ParameterGuide_E_conditional.book 30 ページ 013年10月11日 金曜日 午後8時18分