1.3  Parameter Table
52  YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
14 Fault Reset
Closed: Resets faults if the cause is cleared and the Run command is removed.
175
15 Fast Stop (N.O.)
Closed: Decelerates at the Fast Stop time set to C1-09.
175
16 Motor 2 Selection
Open: Motor 1
Closed: Motor 2
176
17 Fast Stop (N.C.)
Open: Decelerates to stop at the Fast Stop time set to C1-09.
175
18 Timer Function Input
Triggers the timer set up by parameters b4-01 and b4-02. Must be set in conjunction 
with the timer function output (H2- = 12).
176
19 PID Disable
Open: PID control enabled
Closed: PID control disabled
176
1A Accel/Decel Time Selection 2
Used in conjunction with an input terminal set for “Accel/decel time selection 1” 
(H1- = 7), and allows the drive to switch between accel/decel times 3 and 4.
176
1B Program Lockout
Open: Parameters cannot be edited (except for U1-01 if the reference source is assigned 
to the digital operator).
Closed: Parameters can be edited and saved.
176
1E Reference Sample Hold
Closed: Samples the analog frequency reference and operates the drive at that speed.
176
20 to 2F External Fault 
20: N.O., Always detected, ramp to stop
21: N.C., Always detected, ramp to stop
22: N.O., During run, ramp to stop
23: N.C., During run, ramp to stop
24: N.O., Always detected, coast to stop
25: N.C., Always detected, coast to stop
26: N.O., During run, coast to stop
27: N.C., During run, coast to stop
28: N.O., Always detected, Fast Stop
29: N.C., Always detected, Fast Stop
2A: N.O., During run, Fast Stop
2B: N.C., During run, Fast Stop
2C: N.O., Always detected, alarm only (continue running)
2D: N.C., Always detected, alarm only (continue running)
2E: N.O., During run, alarm only (continue running)
2F: N.C., During run, alarm only (continue running)
177
30 PID Integral Reset
Closed: Resets the PID control integral value.
178
31 PID Integral Hold
Open: Performs integral operation. 
Closed: Maintains the current PID control integral value.
178
32 Multi-Step Speed Reference 4
The values set in d1-01 to d1-16 (frequency references) can be selected according to the 
combination of the four terminals set for Multi-Step Speed References 1 to 4.
178
33 Thermostatic Switch (N.C.)
Closed: Closes when thermostatic switches are OFF, and then a TME2 (Transformer 
Temperature DI Fault) fault occurs. 
178
H1 Contact Input Selections
H1- 
Setting
Function Description
Reference 
Page
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
MV1000ParameterGuide_E_conditional.book  52 ページ  2013年10月11日 金曜日 午後8時18分