H1 Contact Input Selections
H1-
Setting
Function Description
Reference
Page
1 LOCAL/REMOTE Selection
Open: REMOTE (parameter settings determine the source of the frequency Reference 1
or 2 (b1-01, b1-02 or b1-15, b1-16))
Closed: LOCAL, frequency reference and Run command are input from the digital
operator.
172
2
External Reference 1/2
Selection
Open: Run command and frequency reference source 1 (determined by b1-01 and
b1-02)
Closed: Frequency Reference Selection 2 (b1-15), Run Command Selection 2 (b1-16)
172
3 Multi-Step Speed Reference 1
When contact input terminals are set to Multi-Step Speed References 1 through 3,
switching combinations of those terminals will create a multi-step speed sequence
using the frequency references set in d1-01 through d1-08.
172
4 Multi-Step Speed Reference 2
5 Multi-Step Speed Reference 3
6 Jog Reference Selection
Closed: Jog frequency reference (d1-17) selected. Jog has priority over all other
reference sources.
172
7 Accel/Decel Time Selection 1
Used to switch between accel/decel time 1 (set in C1-01, C1-02) and accel/decel time 2
(set in C1-03, C1-04).
The combination with H1- = 1A (Accel/Decel Time Selection) allows the drive to
switch between accel/decel time 3 and accel/decel time 4.
172
8 Baseblock Command (N.O.)
Closed: No drive output
172
9 Baseblock Command (N.C.)
Open: No drive output
172
A Accel/Decel Ramp Hold
Open: Accel/decel is not held
Closed: The drive pauses during acceleration or deceleration and maintains the output
frequency.
173
B Drive Overheat Alarm (oH2)
Closed: Closes when an oH2 alarm occurs
173
C
Analog Terminal Input
Selection
Open: Function assigned by H3-14 is disabled.
Closed: Function assigned by H3-14 is enabled.
173
E ASR Integral Reset
Open: PI control
Closed: Integral reset
173
F Through Mode
Select this setting when using the terminal in a pass-through mode.
The terminal does not trigger a drive function but can be used as contact input for the
controller the drive is connected to.
173
10 Up Command
The drive accelerates when the Up command terminal closes, and decelerates when the
Down command closes. When both terminals are closed or both are open, the drive
holds the frequency reference. The Up and Down commands must always be used in
conjunction with one another.
173
11 Down Command
12 Forward Jog
Closed: Runs forward at the Jog frequency d1-17.
175
13 Reverse Jog
Closed: Runs reverse at the Jog frequency d1-17.
175