1.3 Parameter Table
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide 57
F Through Mode
Set this value when using the terminal in the pass-through mode.
186
10 Minor Fault
Closed: An alarm has been triggered, or the IGBTs have reached 90% of their expected
life span.
186
11 Fault Reset Command Active
Closed: A command has been entered to clear a fault via the contact input terminals or
from the serial network.
186
12 Timer Output
Closed: Timer output.
186
13 Speed Agree 2
Closed: When drive output frequency equals the frequency reference ± L4-04.
186
14 User-set Speed Agree 2
Closed: When the drive output frequency is equal to the value in L4-03 ± L4-04.
187
15 Frequency Detection 3
Closed: When the drive output frequency is less than or equal to the value in
L4-03 ± L4-04.
187
16 Frequency Detection 4
Closed: When the output frequency is greater than or equal to the value in
L4-03 ± L4-04.
188
17 Torque Detection 1 (N.C.)
Open: Overtorque or undertorque has been detected.
186
18 Torque Detection 2 (N.O.)
Closed: Overtorque or undertorque has been detected.
186
19 Torque Detection 2 (N.C.)
Open: Overtorque or undertorque has been detected.
186
1A During Reverse
Closed: Drive is running in the reverse direction.
188
1B During Baseblock (N.C.)
Open: Drive has entered the baseblock state (no output voltage).
189
1C Motor 2 Selection
Closed: Motor 2 is selected by a contact input (H1- = 16).
189
1D During Regeneration
Closed: Motor is regenerating energy into the drive.
189
1E Restart Enabled
Closed: An automatic restart is performed
189
1F Motor Overload Alarm (oL1)
Closed: oL1 is at 90% of its trip point or greater. An oH3 situation also triggers this
alarm.
189
20
Drive Overheat Pre-Alarm
(oH)
Closed: Thermistor temperature exceeds the parameter L8-02 value.
189
21 User-Set Alarm
Closed: Alarm selected to H2-18 occurred.
Note: This setting is available from the drive software versions S0108 and later.
189
22
Mechanical Weakening
Detection (N.O.)
Closed: Mechanical weakening detected.
189
H2 Contact Output Settings
H2-
Setting
Function Description Page
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common
CLV
V/f
OLV
common
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_