1.3 Parameter Table
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide 73
o1-03
(502H)
Frequency
Reference Setting/
Display Unit
Sets the units the drive should use to display the frequency reference and
motor speed monitors.
0: 0.01 Hz
1: 0.01% (100% = E1-04)
2: r/min
(calculated using the number of motor poles setting in E2-04, E4-04,
or E5-04)
3: User-selected units (set by o1-10 and o1-11)
Default: <10>
Min: 0
Max: 3
232
o1-04
(503H)
V/f Pattern
Frequency
Parameter Setting
Unit
0: Hz
1: r/min
Default:
<10>
Min: 0
Max: 1
233
o1-10
(520H)
User-Set Display
Units Maximum
Val ue
These settings define the display values when o1-03 is set to 3.
o1-10 sets the display value that is equal to the maximum output frequency.
o1-11 sets the position of the decimal position.
Default:
<36>
Min: 1
Max: 60000
233
o1-11
(521H)
User-set Display
Units Decimal
Display
Default:
<36>
Min: 0
Max: 3
233
o2: Digital Operator Keypad Functions
o2-01
(505H)
LO/RE Key
Function Selection
0: Disabled
1: Enabled. LO/RE key switches between LOCAL and REMOTE operation.
Default: 1
Min: 0
Max: 1
233
o2-02
(506H)
STOP Key Function
Selection
0: Disabled. STOP key is disabled in REMOTE operation.
1: Enabled. STOP key is always enabled.
Default: 1
Min: 0
Max: 1
234
o2-03
(507H)
User Parameter
Default Value
0: No change.
1: Set defaults. Saves parameter settings as default values for a User
Initialization.
2: Clear all. Clears the default settings that have been saved for a User
Initialization.
Default: 0
Min: 0
Max: 2
234
o2-04
(508H)
Drive Model
Selection
Enter the drive model. Setting required only if installing a new control
board.
Default:
Determined by
drive capacity
Min: –
Max: –
234
o2-05
(509H)
Frequency
Reference Setting
Method Selection
0: ENTER key must be pressed to enter a frequency reference.
1: ENTER key is not required. The frequency reference can be adjusted
using the up and down arrow keys only.
Default: 0
Min: 0
Max: 1
234
o2-06
(50AH)
Operation Selection
when Digital
Operator is
Disconnected
0: The drive continues operating if the digital operator is disconnected.
1: A fault is triggered (oPr) and the motor coasts to stop.
Default: 0
Min: 0
Max: 1
235
o2-07
(527H)
Motor Direction at
Power Up when
Using Operator
0: Forward
1: Reverse
This parameter requires that drive operation be assigned to the digital
operator.
Default: 0
Min: 0
Max: 1
235
o2-09
(50DH)
Initialization Mode
0: Japan
1: America
2: Europe
3: China
De
fault: 0
Min: 0
Max: 3
o2-11
(5
0FH)
Reference Voltage
for Input Voltage
Detection
Sets the primary rated voltage of the transformer.
Default:
<6>
Min: 0 V
Max: 20000 V
235
No.
(Addr.)
Name Description Setting Page
All Modes
common_
CLV
V/f
OLV
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
MV1000ParameterGuide_E_conditional.book 73 ページ 013年10月11日 金曜日 午後8時18分

Table of Contents

Other manuals for YASKAWA FSDrive-MV1000

Related product manuals