1.3 Parameter Table
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide 79
U1-49
(30C0H)
Output
Zero-phase
Vo l t a g e
Displays the detected zero-phase voltage at the output side.
10 V: Drive
rated voltage
1 V –
U1-52
(1081H)
Output Voltage
Displays the detected output voltage value.
10 V: Drive
rated voltage
1 V –
U1-54
(1083H)
Input Voltage
Displays the detected input voltage value (compatible with option cards).
10 V: Input
reference
voltage (o2-11)
1 V –
U1-55
(1084H)
Input Current
Displays the detected input current value (compatible with option cards).
10 V: Drive
rated current
0.1 A –
U2: Fault Trace
U2-01
(80H)
Current Fault
Displays the current fault.
No signal output
available
––
U2-02
(81H)
Previous Fault
Displays the previous fault.
No signal output
available
––
U2-03
(82H)
Frequency
Reference at
Previous Fault
Displays the frequency reference at the previous fault.
No signal output
available
0.01 Hz –
U2-04
(83H)
Output
Frequency at
Previous Fault
Displays the output frequency at the previous fault.
No signal output
available
0.01 Hz –
U2-05
(84H)
Output Current
at Previous Fault
Displays the output current at the previous fault.
No signal output
available
0.1 A –
U2-06
(85H)
Motor Speed at
Previous Fault
Displays the motor speed at the previous fault.
No signal output
available
0.01 Hz –
U2-07
(86H)
Output Voltage at
Previous Fault
Displays the output voltage at the previous fault.
No signal output
available
1 V –
U2-08
(87H)
DC Bus Voltage
at Previous Fault
Displays the DC bus voltage at the previous fault.
No signal output
available
1 V
–
U2-09
(88H)
Output Power at
Pre
vious Fault
Displays the output power at the previous fault.
No signal output
available
1 kW –
U2-10
(89H)
Torque
Reference at
Previous Fault
Displays the torque reference at the previous fault.
No signal output
available
0.1% –
U2-11
(8AH)
Input Terminal
Status at
Previous Fault
Displays the input terminal status at the previous fault. Displays the same
status as U1-10.
No signal output
available
––
U2-12
(8BH)
Output Terminal
Status at
Previous Fault
Displays the output terminal status at the previous fault. Displays the same
status as U1-11.
No signal output
available
––
U2-13
(8CH)
Drive Operation
Status at
Previous Fault
Displays the operation status of the drive at the previous fault. Displays
the same status as U1-12.
No signal output
available
––
U2-14
(8DH)
Cumulative
Operation Time
at Previous Fault
Displays the cumulative operation time at the previous fault.
No signal output
available
1 h –
U2-15
(7E0H)
Soft Starter
Speed Reference
at Previous Fault
Displays the speed reference for the soft starter at the previous fault.
No signal output
available
0.01 Hz –
U2-16
(7E1H)
Motor q-Axis
Current at
Previous Fault
Displays the q-axis current for the motor at the previous fault.
No signal output
available
0.1% –
No.
(Addr.)
Name Description
Analog Output
Level
Unit Page
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
MV1000ParameterGuide_E_conditional.book 79 ページ 2013年10月11日 金曜日 午後8時18分