1.3 Parameter Table
80 YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
U2-17
(7E2H)
Motor d-Axis
Current at
Previous Fault
Displays the d-axis current for the motor at the previous fault.
No signal output
available
0.1%
U2-18
(7E3H)
ASR Output at
Previous Fault
Displays the ASR output at the previous fault.
No signal output
available
0.01%
U2-20
(8EH)
IGBT
Temperature at
Previous Fault
Displays the temperature of the IGBTs at the previous fault.
No signal output
available
1°C–
U2-28
(7FCH)
Malfunctioned
Cell
Displays the Power Cell at which a fault has occurred in hexadecimal.
No signal output
available
––
U2-29
(30E0H)
Output
Zero-phase
Voltage at
Previous Fault
Displays the detected zero-phase voltage at the output side at the previous
fault.
10 V: Drive
rated voltage
1 V
U2-30
(30E1H)
Output Voltage at
Previous Fault
Displays the detected output voltage value at the previous fault.
10 V: Drive
rated voltage
1 V
U2-31
(30E2H)
Input Voltage at
Previous Fault
Displays the detected input voltage value at the previous fault.
10 V: Input
reference
voltage
1 V
U3: Fault History
U3-01 to
U3-49
(3140H to
3170H)
First to 49th
Most Recent
Fault
Displays the 1st to the 49th most recent faults.
After 49 faults have occurred in the drive, the data for the oldest fault is
deleted. The most recent fault appears in U3-01, with the next most recent
fault appearing in U3-02. The data is moved to the next monitor parameter
every time a fault occurs.
No signal output
available
––
U3-51 to
U3-99
(3172H to
31A2H)
Cumulative
Operation Time
at 1st to 49th
Most Recent
Fault
Displays the cumulative operation time when the 1st to the 49th most
recent faults occurred.
No signal output
ava
ilable
1 h
U4: Maintenance Monitors
U4-01
(4CH)
Cumulative
Operation Time
Displays the cumulative operation time of the drive. The value for the
cumulative operation time counter can be reset in parameter o4-01.
Use parameter o4-02 to determine if the operation time should start as
soon as the power is switched on or only while the Run command is ON.
The maximum number displayed is 99999, after which the value is reset to
0.
No signal output
available
1 h
U4-02
(75H)
Number of Run
Commands
Displays the number of times the Run command is entered. Reset the
number of Run commands using parameter o4-13. This value will reset to
0 and start counting again after reaching 65535.
No signal output
available
1 Time
U4-08
(68H)
IGBT
Temperature
Displays the power cell with the highest IGBTs temperature.
10 V: 100°C1°C–
U4-10
(5CH)
kWh, Lower 4
Digits
Monitors the drive output power. The value is shown as a 9-digit number
displayed across two monitor parameters, U4-10 and U4-11.
Example:
12345678.9 kWh is displayed as:
U4-10: 678.9 kWh
U4-11: 12345 MWh
No signal output
available
0.1
kWh
U4-11
(5DH)
kWh, Upper 5
Digits
No signal output
available
1 MWh
U4-13
(7CFH)
Peak Hold
Current
Displays the highest current value that occurred during run.
No signal output
available
0.1 A
No.
(Addr.)
Name Description
Analog Output
Level
Unit Page
CLV
V/f
OLV
common
All Modes
common
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_