1.3  Parameter Table
80  YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
U2-17
(7E2H)
Motor d-Axis 
Current at 
Previous Fault
Displays the d-axis current for the motor at the previous fault.
No signal output 
available
0.1% –
U2-18
(7E3H)
ASR Output at 
Previous Fault
Displays the ASR output at the previous fault.
No signal output 
available
0.01% –
U2-20
(8EH)
IGBT 
Temperature at 
Previous Fault
Displays the temperature of the IGBTs at the previous fault.
No signal output 
available
1°C–
U2-28
(7FCH)
Malfunctioned 
Cell
Displays the Power Cell at which a fault has occurred in hexadecimal.
No signal output 
available
––
U2-29
(30E0H)
Output 
Zero-phase 
Voltage at 
Previous Fault
Displays the detected zero-phase voltage at the output side at the previous 
fault.
10 V: Drive 
rated voltage
1 V –
U2-30
(30E1H)
Output Voltage at 
Previous Fault
Displays the detected output voltage value at the previous fault.
10 V: Drive 
rated voltage
1 V –
U2-31
(30E2H)
Input Voltage at 
Previous Fault
Displays the detected input voltage value at the previous fault.
10 V: Input 
reference 
voltage
1 V –
U3: Fault History 
U3-01 to 
U3-49
(3140H to 
3170H)
First to 49th 
Most Recent 
Fault
Displays the 1st to the 49th most recent faults.
After 49 faults have occurred in the drive, the data for the oldest fault is 
deleted. The most recent fault appears in U3-01, with the next most recent 
fault appearing in U3-02. The data is moved to the next monitor parameter 
every time a fault occurs.
No signal output 
available
––
U3-51 to 
U3-99
(3172H to 
31A2H)
Cumulative 
Operation Time 
at 1st to 49th 
Most Recent 
Fault
Displays the cumulative operation time when the 1st to the 49th most 
recent faults occurred.
No signal output 
ava
ilable
1 h –
U4: Maintenance Monitors
U4-01
(4CH)
Cumulative 
Operation Time
Displays the cumulative operation time of the drive. The value for the 
cumulative operation time counter can be reset in parameter o4-01.
Use parameter o4-02 to determine if the operation time should start as 
soon as the power is switched on or only while the Run command is ON. 
The maximum number displayed is 99999, after which the value is reset to 
0.
No signal output 
available
1 h –
U4-02
(75H)
Number of Run 
Commands
Displays the number of times the Run command is entered. Reset the 
number of Run commands using parameter o4-13. This value will reset to 
0 and start counting again after reaching 65535.
No signal output 
available
1 Time –
U4-08
(68H)
IGBT 
Temperature
Displays the power cell with the highest IGBTs temperature.
10 V: 100°C1°C–
U4-10
(5CH)
kWh, Lower 4 
Digits
Monitors the drive output power. The value is shown as a 9-digit number 
displayed across two monitor parameters, U4-10 and U4-11.
Example:
12345678.9 kWh is displayed as:
U4-10: 678.9 kWh
U4-11: 12345 MWh
No signal output 
available
0.1 
kWh
–
U4-11
(5DH)
kWh, Upper 5 
Digits
No signal output 
available
1 MWh –
U4-13
(7CFH)
Peak Hold 
Current
Displays the highest current value that occurred during run.
No signal output 
available
0.1 A –
No.
(Addr.)
Name Description
Analog Output 
Level
Unit Page
CLV
V/f
OLV
MV1000ParameterGuide_E_conditional.book  80 ページ  2013年10月11日 金曜日 午後8時18分