1.5 Defaults by Drive Model Selection (o2-04)
92 YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
Table 1.8 11 kV Class Drives Default Settings by Drive Model Selection
No. <61> Name Unit Default Settings
–
Model
CIMR-MV2
– 035 050 070 100 140 200 260 330 400 520 650
o2-04
Drive Model
Selection
– 80 81 82 83 84 85 86 87 88 89 8A
E2-11 (E4-11)
<61> Parameter numbers shown in parenthesis are valid for motor 2.
<62> The alarm detection level differs for each drive model because of the different thermistor position on each drive.
Motor Rated Power kW 530 760 1070 1520 2130 3050 3960 5030 6100 7930 9910
b3-04
V/f Gain during Speed
Search
%8080808080808080808080
b3-06
Output Current 1 during
Speed Search
– 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-11
Speed Search Method
Switching Level (Speed
Estimate Type Speed
Search)
% 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
E2-01 (E4-01) Motor Rated Current A 30.0 45.0 60.0 85.0 120.0 170.0 220.0 280.0 340.0 440.0 550.0
E2-02 (E4-02) Motor Rated Slip Hz 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25
E2-03 (E4-03) Motor No-Load Current A 8.0 11.0 15.0 21.0 30.0 43.0 55.0 70.0 85.0 110.0 138.0
E2-05 (E4-05)
Motor Line-to-Line
Resistance
W 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300
E2-06 (E4-06)
Motor Leakage
Inductance
% 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0
E2-10 (E4-10)
Motor Iron Loss for
Torque Compensation
W00000000000
L2-02
Momentary Power Loss
Ride-Thru Time
s 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
L2-03
Momentary Power Loss
Ride-Thru Minimum
Baseblock Time
s 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
L2-04
Momentary Power Loss
Ride-Thru Voltage
Recovery Time
s 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
L2-05
Undervoltage Detection
Level (Uv)
V 1188 1188 1188 1188 1188 1188 1188 1188 1188 1188 1188
L8-02
<62> Overheat Alarm Level – 105 105 105 105 105 105 95 105 105 100 105
L8-09
Output Ground Fault
Detection Selection
–11111111111
L8-33
FAN Board Use
Selection
–22222222222
L8-87
Transformer Overheat
Alarm (TMA) Level
°C 130 130 130 130 130 130 130 130 130 130 130
L8-88
Transformer Overheat
Fault (TME) Level
°C 140 140 140 140 140 140 140 140 140 140 140
n1-03
Hunting Prevention
Time Constant
ms 30 30 30 30 30 30 30 30 30 30 30
n9-02
Output Current
Detection Gain
– 100 100 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000
n9-71
Input Current
Conversion Coefficient
– 0.0340 0.0340 0.0235 0.0150 0.0110 0.0094 0.0060 0.0060 0.0040 0.0040 0.0030
o2-11
Reference Voltage for
Input Voltage Detection
V 11000 11000 11000 11000 11000 11000 11000 11000 11000 11000 11000
MV1000ParameterGuide_E_conditional.book 92 ページ 2013年10月11日 金曜日 午後8時18分