3.6 Control Circuit Wiring
70 YASKAWA ELECTRIC EZZ010928 FSDrive-MV1000 Instructions
Note: Depending on a parameter setting, either one or two boards can be inserted. In this table, it is assumed that one board is inserted.
Sequence output
terminals
30
Major fault
Transfer contact relay
220 Vac/15 A,
110 Vac/15 A,
24 Vdc/15 A
Open: Major fault (32-31)
Closed: Major fault (32-30)
31
32
33
During run
Transfer contact relay
220 Vac/15 A,
110 Vac/15 A,
24 Vdc/15 A
Closed: During run (35-33)
Open: During run (35-34)
34
35
36
Drive ready
Transfer contact relay
220 Vac/15 A,
110 Vac/15 A,
24 Vdc/15 A
Closed: Drive ready (38-36)
Open: Drive ready (38-37)
37
38
39
Minor fault
N.O. contact relay
220 Vac/15 A,
110 Vac/15 A,
24 Vdc/15 A
Closed: Minor fault
40
41
Medium-voltage power
shutdown command
N.C. contact output
220 Vac/4 A,
110 Vac/7 A
200 Vdc/4 A
100 Vdc/7 A
Closed (N.C.): Turning off
(closed when power is off)
42
Terminals for
inrush current
suppression
circuit
26
Inrush current suppression
circuit (option)
N.O. contact relay output
220 Vac/5.5 A,
110 Vac/10 A,
100 Vdc/0.5 A
<1>
MC_ON signal
(Output in response to Drive
Ready)
28
27
N.C. contact relay output
220 Vac/10 A,
24 Vdc/10 A
28
L47
Contact output
220 Vac/8 mA
MC_ANS signal
(Closed by answer from inrush
current suppression panel)
L48
Terminals for
the PG <2>
L19
Line driver
PG interface PG-X3
(Option)
A pulse signal input
Inputs the A and B signals
Signal levels: Equivalent to RS-422
L20 A inverse signal input
L21 B pulse signal input
L22 B inverse signal input
L23 PG power supply
Output voltage:
12 V ± 5% or 5.5 V ± 5%
Max. output current: 200 mA
L24 PG power supply common
L25 Ground Grounds shielded lines
L19
Complementary type
PG interface PG-B3
(Option)
A+ pulse signal input
Inputs the A and B channel
Signal levels: High level: 8 to 12 V
Low level: 2.0 V or less
L20 A- pulse signal input
L21 B+ pulse signal input
L22 B- pulse signal input
L23 PG power supply
Output voltage: 12 V ± 5%
Max. output current: 200 mA
L24 PG power supply common
L25 Ground Grounds shielded lines
<1> For the host breaker, AC voltage should be input.
If using DC voltage as the input power, install a relay that has contacts with a large capacity.
<2> When a PG interface is mounted, either a line driver PG interface or a complementary type PG interface is prepared.
Type Terminal Signal Name Signal Level Terminal Function