EasyManua.ls Logo

YASKAWA HV600

YASKAWA HV600
794 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.3 C: Tuning
232 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Note:
When the wiring length for bypass models B001 to B007 is more than 10 m, you must decrease the carrier frequency or output current.
C6-03: Carrier Frequency Upper Limit
No.
(Hex.)
Name Description
Default
(Range)
C6-03
(0225)
Carrier Frequency Upper
Limit
Sets the upper limit of the carrier frequency. Set C6-02 = F [Carrier Frequency Selection = User
Defined (C6-03 to C6-05)] to set this parameter.
Determined by C6-02
(1.0 - 12.5 kHz)
Setting a Fixed User-Defined Carrier Frequency
When you cannot use C6-02 to set a carrier frequency between set selectable values, you can set the value in C6-03.
The carrier frequency will be fixed to the value set to C6-03.
Set C6-03 = C6-04 [Carrier Frequency Lower Limit] to fix the carrier frequency.
Setting a Variable Carrier Frequency to Agree with the Output Frequency
Set C6-03, C6-04, and C6-05 [Carrier Freq Proportional Gain] as shown in Figure 5.31 to make the carrier
frequency change linearly with the output frequency.
C6-03: Carrier Frequency Upper Limit
C6-04: Carrier Frequency Lower Limit
C6-05: Carrier Freq Proportional Gain
E1-04: Maximum Output Frequency
Figure 5.31 Setting a Variable Carrier Frequency to Agree with the Output Frequency
Note:
When C6-05 7, the drive disables C6-04. The carrier frequency is fixed to the value set to C6-03.
If these conditions are true at the same time, the drive will detect oPE11 [Carrier Frequency Setting Error]:
C6-05 6
C6-04 C6-03
C6-04: Carrier Frequency Lower Limit
No.
(Hex.)
Name Description
Default
(Range)
C6-04
(0226)
Carrier Frequency Lower
Limit
Sets the lower limit of the carrier frequency. Set C6-02 = F [Carrier Frequency Selection = User
Defined (C6-03 to C6-05)] to set this parameter.
Determined by C6-02
(1.0 - 12.5 kHz)
Set C6-03 [Carrier Frequency Upper Limit], C6-04, and C6-05 [Carrier Freq Proportional Gain] to make the carrier
frequency change linearly with the output frequency.
Note:
If these conditions are true at the same time, the drive will detect oPE11 [Carrier Frequency Setting Error]:
C6-04 C6-03
C6-05 6
C6-05: Carrier Freq Proportional Gain
No.
(Hex.)
Name Description
Default
(Range)
C6-05
(0227)
Carrier Freq Proportional
Gain
Sets the proportional gain for the carrier frequency. Set C6-02 = F [Carrier Frequency Selection =
User Defined (C6-03 to C6-05)] to set this parameter.
Determined by C6-02
(0 - 99)
Set C6-03 [Carrier Frequency Upper Limit], C6-04 [Carrier Frequency Lower Limit], and C6-05 to make the carrier
frequency change linearly with the output frequency.

Table of Contents