5.4 d: References
236 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Note:
• The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change. Calculate the upper limit value with this formula:
Upper limit value = (E1-04) × (d2-01) / 100
• To set d1-01 to 1-step speed parameter in a multi-step speed operation, set b1-01 = 0 [Frequency Reference Selection 1 = Keypad].
â– d1-02: Reference 2
No.
(Hex.)
Name Description
Default
(Range)
d1-02
(0281)
RUN
Reference 2 Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection]. 0.00 Hz
(0.00 - 400.00 Hz)
Note:
• The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
• To set d1-02 to Multi-Step Speed 2, set H3-02 and H3-10 ≠2 [MFAI Function Select ≠Auxiliary Frequency Reference 1].
â– d1-03: Reference 3
No.
(Hex.)
Name Description
Default
(Range)
d1-03
(0282)
RUN
Reference 3 Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection]. 0.00 Hz
(0.00 - 400.00 Hz)
Note:
• The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
• To set d1-03 to Multi-Step Speed 3, set H3-02 and H3-10 ≠3 [MFAI Function Select ≠Auxiliary Frequency Reference 2].
â– d1-04: Reference 4
No.
(Hex.)
Name Description
Default
(Range)
d1-04
(0283)
RUN
Reference 4 Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection]. 0.00 Hz
(0.00 - 400.00 Hz)
Note:
• The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
• This parameter sets the frequency reference of Multi-Step Speed 4.
â– d1-05: Reference 5
No.
(Hex.)
Name Description
Default
(Range)
d1-05
(0284)
RUN
Reference 5 Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection]. 0.00 Hz
(0.00 - 400.00 Hz)
Note:
• The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
• This parameter sets the frequency reference of Multi-Step Speed 5.
â– d1-06: Reference 6
No.
(Hex.)
Name Description
Default
(Range)
d1-06
(0285)
RUN
Reference 6 Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection]. 0.00 Hz
(0.00 - 400.00 Hz)