Parameter Details
5
5.5 E: Motor Parameters
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference 245
Use this constant torque pattern for general applications. Use this pattern when the load torque is constant without any
rotation speed, for example with linear conveyor systems.
Note:
The voltage values in the figures are for 208/240 V. Multiply the values by 2 for 480 V.
D002 - D016, A002 - A015, B001 - B007 D024 - D169, A022 - A154, B011 - B077 A192 - A248, B096 - B302
1 : Const Trq, 60Hz base, 60Hz max
Use this constant torque pattern for general applications. Use this pattern when the load torque is constant without any
rotation speed, for example with linear conveyor systems.
Note:
The voltage values in the figures are for 208/240 V. Multiply the values by 2 for 480 V.
D002 - D016, A002 - A015, B001 - B007 D024 - D169, A022 - A154, B011 - B077 A192 - A248, B096 - B302
2 : Const Trq, 50Hz base, 60Hz max
Use this constant torque pattern for general applications. Use this pattern when the load torque is constant without any
rotation speed, for example with linear conveyor systems.
Note:
The voltage values in the figures are for 208/240 V. Multiply the values by 2 for 480 V.
D002 - D016, A002 - A015, B001 - B007 D024 - D169, A022 - A154, B011 - B077 A192 - A248, B096 - B302
3 : Const Trq, 60 Hz base, 72 Hz max
Use this constant torque pattern for general applications. Use this pattern when the load torque is constant without any
rotation speed, for example with linear conveyor systems.
Note:
The voltage values in the figures are for 208/240 V. Multiply the values by 2 for 480 V.