5.5 E: Motor Parameters
244 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Note:
Be aware of the following points when manually setting V/f patterns.
To set linear V/f characteristics at frequencies lower than E1-06 [Base Frequency], set E1-07 = E1-09 [Mid Point A Frequency = Minimum
Output Frequency]. In this application, the drive ignores E1-08 [Mid Point A Voltage].
Set the five frequencies as specified by these rules: Incorrect settings will cause oPE10 [V/f Data Setting Error].
E1-09 E1-07 < E1-06 E1-11 E1-04 [Minimum Output Frequency Mid Point A Frequency < Base Frequency Mid Point B
Frequency Maximum Output Frequency]
Setting E1-11 = 0 [Mid Point B Frequency = 0 Hz] disables E1-12 [Mid Point B Voltage]. Ensure that the four frequencies are set
according to the following rules;
E1-09 E1-07 < E1-06 E1-04
When you use A1-03 [Initialize] to initialize the drive, it will not reset E1-03.
Figure 5.38 V/f Pattern
E1-01: Input AC Supply Voltage
No.
(Hex.)
Name Description
Default
(Range)
E1-01
(0300)
Input AC Supply Voltage Sets the drive input voltage. 208/240 V: 240 V,
480 V: 480 V
(208/240 V: 155 - 255 V,
480 V: 310 - 510 V)
NOTICE: Set parameter E1-01 to align with the drive input voltage (not motor voltage). If this parameter is incorrect, the protective
functions of the drive will not operate correctly and it can cause damage to the drive.
Values Related to the Drive Input Voltage
The value set in E1-01 is the base value that the drive uses for the motor protective functions in Table 5.34. With a
480 V drive, the detection level changes for some motor protective functions.
Table 5.34 Values Related to the Drive Input Voltage
Voltage E1-01 Setting
Approximate Values
ov Detection Level
L2-05
[Undervoltage Detection Lvl
(Uv1)]
L3-17
[DC Bus Regulation Level]
208/240 V All settings 410 V 190 V 375 V
480 V
Setting value 400 V 820 V 380 V 750 V
Setting value < 400 V 820 V 350 V 750 V
E1-03: V/f Pattern Selection
No.
(Hex.)
Name Description
Default
(Range)
E1-03
(0302)
V/f Pattern Selection Sets the V/f pattern for the drive and motor. You can use one of the preset patterns or you can make a
custom pattern.
F
(0 - F)
Note:
Set the correct V/f pattern for the application and operation area. An incorrect V/f pattern can decrease motor torque and increase current
from overexcitation.
Parameter A1-03 [Initialize Parameters] will not initialize the value of E1-03.
0 : Const Trq, 50Hz base, 50Hz max