Parameter Details
5
5.7 H: Terminal Functions
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference 309
Figure 5.66 Drive Transmit Wait Time
H5-08: Communication Protocol Selection
No.
(Hex.)
Name Description
Default
(Range)
H5-08
(062D)
Communication Protocol
Selection
Selects the communication protocol. 3
(0 - 3)
0 : Modbus/MEMOBUS
1 : Metasys/N2
2 : Apogee/P1
3 : BACnet
H5-09: CE Detection Time
No.
(Hex.)
Name Description
Default
(Range)
H5-09
(0435)
CE Detection Time Sets the detection time for CE [Modbus Communication Error] issues when communication stops. 2.0 s
(0.0 - 10.0 s)
H5-10: Modbus Register 0025H Unit Sel
No.
(Hex.)
Name Description
Default
(Range)
H5-10
(0436)
Modbus Register 0025H
Unit Sel
Sets the unit of measure used for the MEMOBUS/Modbus communications monitor register 0025H
(output voltage reference monitor).
0
(0, 1)
0 : 0.1 V units
1 : 1 V units
H5-11: Comm ENTER Command Mode
No.
(Hex.)
Name Description
Default
(Range)
H5-11
(043C)
Comm ENTER Command
Mode
Sets the function to make the Enter command necessary to change parameters through MEMOBUS/
Modbus communications.
0
(0, 1)
0 : ENTER Command Required
You must use the Enter command to enable changes to parameters. Make all parameter changes then input the Enter
command.
1 : ENTER Command Not Required
It is not necessary to input the Enter command to change parameters.
H5-14: BACnet Device Obj ID LOW BITS
No.
(Hex.)
Name Description
Default
(Range)
H5-14
(310D)
BACnet Device Obj ID
LOW BITS
Sets the lower bits of the BACnet device object ID as a 4-digit hexadecimal number. 0001
(0000 - FFFF)