Parameter Details
5
5.7 H: Terminal Functions
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference 313
Figure 5.68 Virtual Digital I/O Functional Block Diagram
Note:
Refer to H1-xx MFDI Setting Values for more information on the virtual digital input setting values.
Refer to H2-xx MFDO Setting Values for more information on the virtual digital output setting values.
Refer to H3-xx MFAI Setting Values for more information on the virtual analog input setting values.
Refer to H4-xx MFAO Setting Values for more information on the virtual analog output setting values.
You cannot set 0 [3-Wire Sequence] and 20 or 2F [External Fault] to H7-01 to H7-04 [Virtual Multi-Function Input 1 to 4].
If you will not use the terminal, set H7-01 to H7-04 = F. This function does not support the through mode function.
H7-00: Virtual MFIO selection
No.
(Hex.)
Name Description
Default
(Range)
H7-00
(116F)
Expert
Virtual MFIO selection Sets the function to enable and disable the virtual I/O function. Set this parameter to 1 to operate the
virtual I/O function.
0
(0, 1)
0 : Disabled
1 : Enabled
H7-01: Virtual Multi-Function Input 1
No.
(Hex.)
Name Description
Default
(Range)
H7-01
(1185)
Expert
Virtual Multi-Function Input
1
Sets the function that enters the virtual input set in H7-10 [Virtual Multi-Function Output 1]. F
(1 - 1B8)
Note:
Settings 1B [Programming Lockout] and 11B [!Programming Lockout] are not available.
H7-02: Virtual Multi-Function Input 2
No.
(Hex.)
Name Description
Default
(Range)
H7-02
(1186)
Expert
Virtual Multi-Function Input
2
Sets the function that enters the virtual input set in H7-12 [Virtual Multi-Function Output 2]. F
(1 - 1B8)
Note:
Settings 1B [Programming Lockout] and 11B [!Programming Lockout] are not available.
H7-03: Virtual Multi-Function Input 3
No.
(Hex.)
Name Description
Default
(Range)
H7-03
(1187)
Expert
Virtual Multi-Function Input
3
Sets the function that enters the virtual input set in H7-14 [Virtual Multi-Function Output 3]. F
(1 - 1B8)
Note:
Settings 1B [Programming Lockout] and 11B [!Programming Lockout] are not available.
H7-01
[Virtual Multi-Function
Input 1]
H7-11
[Virtual Output
1 Delay Time]
H7-10
[Virtual Multi-Function
Output 1]

Table of Contents

Other manuals for YASKAWA HV600

Related product manuals