5.10 o: Keypad-Related Settings
364 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
o2-04 Setting Drive Model
A6 4156
A7 4180
o2-04 Setting Drive Model
A8 4240
A9 4302
â–  o2-05: Home Mode Freq Ref Entry Mode
No.
(Hex.)
Name Description
Default
(Setting Range)
o2-05
(0509)
Home Mode Freq Ref Entry
Mode
Sets the function that makes it necessary to push to use the keypad to change the frequency
reference value while in Drive Mode.
0
(0, 1)
0 : ENTER Key Required
You must push to use the keypad to change the frequency reference value.
1 : Immediate / MOP-style
The frequency reference changes when you enter it with the keypad. This then changes the output frequency. It is not
necessary to push . The drive keeps the frequency reference for 5 seconds after you use and on the
keypad to change the frequency reference value.
â–  o2-06: Keypad Disconnect Detection
No.
(Hex.)
Name Description
Default
(Range)
o2-06
(050A)
Keypad Disconnect
Detection
Sets the function that stops the drive if you disconnect the keypad connection cable from the drive or
if you damage the cable while the keypad is the Run command source.
1
(0, 1)
If the keypad installed to the drive is disconnected, this parameter will continue to operate.
This parameter is enabled in these conditions:
• b1-02 = 0 [Run Command Selection 1 = Keypad]
• In HAND Mode
0 : Disabled
The drive continues operation if it detects a keypad disconnection.
1 : Enabled
When the drive detects a keypad disconnection, the drive detects oPr [Keypad Connection Fault], and stops
operation. The motor coasts to stop.
â–  o2-09: Region Code
No.
(Hex.)
Name Description
Default
(Range)
o2-09
(050D)
Reserved - -
â–  o2-19: Parameter Write during Uv
No.
(Hex.)
Name Description
Default
(Range)
o2-19
(061F)
Parameter Write during Uv Enables and disables the function to change parameter settings during a Uv [DC Bus Undervoltage]
condition.
0
(0, 1)
0 : Disabled
1 : Enabled

Table of Contents

Other manuals for YASKAWA HV600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA HV600 and is the answer not in the manual?

YASKAWA HV600 Specifications

General IconGeneral
CategoryDC Drives
SeriesHV600
Overload Capacity150% for 60 seconds
Output Voltage0 - Input Voltage
EnclosureNEMA 1, NEMA 12
CommunicationEthernet/IP, Modbus, DeviceNet, Profibus
SafetySafe Torque Off (STO)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short Circuit
Humidity5-95% (non-condensing)
AltitudeUp to 1000m (3280ft) without derating
Control MethodVector Control

Related product manuals