9.9 F: Options
614 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
No.
(Hex.)
Name Description
Default
(Range)
Ref.
F7-37
(0379)
Dynamic In Param 5 for
CommCard
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values
from the MEMOBUS/Modbus address registers stored for each parameter to Input
Assembly 166. The drive returns the default register value for the option card when the
MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.
When you use a ProfiNet option, set this parameter to set to configurable input 5.
0 259
F7-38
(037A)
Dynamic In Param 6 for
CommCard
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values
from the MEMOBUS/Modbus address registers stored for each parameter to Input
Assembly 166. The drive returns the default register value for the option card when the
MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.
0 259
F7-39
(037B)
Dynamic In Param 7 for
CommCard
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values
from the MEMOBUS/Modbus address registers stored for each parameter to Input
Assembly 166. The drive returns the default register value for the option card when the
MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.
0 259
F7-40
(037C)
Dynamic In Param 8 for
CommCard
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values
from the MEMOBUS/Modbus address registers stored for each parameter to Input
Assembly 166. The drive returns the default register value for the option card when the
MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.
0 259
F7-41
(037D)
Dynamic In Param 9 for
CommCard
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values
from the MEMOBUS/Modbus address registers stored for each parameter to Input
Assembly 166. The drive returns the default register value for the option card when the
MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.
0 259
F7-42
(037E)
Dynamic In Param 10 for
CommCard
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values
from the MEMOBUS/Modbus address registers stored for each parameter to Input
Assembly 166. The drive returns the default register value for the option card when the
MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.
0 259