Parameter List
9
9.17 Z: Bypass Parameters
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference 667
No.
(Hex.)
Name Description
Default
(Range)
Ref.
Z1-50
(85F7)
Bypass Input Phase Loss
Level
The bypass measures the current unbalance between phases to detect input phase loss.
Sets the current level between phases in Bypass Mode.
Usually it is not necessary to change this parameter.
25.0%
(5.0 - 50.0%)
438
Z1-51
(85F8)
Bypass Input Phase Loss
Delay
Sets the trip time for an input phase loss condition in Bypass Mode.
Note:
When you set this parameter to 0.0, it will disable bypass phase loss detection.
5.0 s
(0.0 - 30.0 s)
438
Z1-52
(85F9)
Input Phase Rotation
Detection
Sets bypass response when the Bypass Mode phase rotation is incorrect.
0 : Disabled
1 : Alarm
2 : Fault
0
(0 - 2)
438
Z1-53
(85FA)
Load Verify Detection Enables and disables verification that the motor is running when commanded to run.
0 : Disabled
1 : Enabled
0
(0, 1)
439
Z1-55
(85FC)
Welded Contactor
Detection
Enables and disables detection of K3 “welded contactor” condition.
0 : Disabled
1 : Enabled
Note:
When Z1-42 = 1 or 2 [Soft Starter Selection = Installed – Coast To Stop or Installed –
Ramp To Stop], the bypass will automatically disable welded contactor detection.
0
(0, 1)
439
Z1-56
(85FD)
RUN
Test Mode Sets the behavior of the drive input contactor K1 during Bypass Mode.
0 : Drive Power Off during Bypass
1 : Drive Power On during Bypass
0
(0, 1)
440
Z1-60
(8601)
Blackout Operation
Select
Sets bypass behavior when contactor voltage is less than Z1-19 [Blackout Voltage Level].
0 : Fault
1 : Restart Delay with Speed Search
2 : Restart Delay from Zero Speed
3 : Disabled
1
(0 - 3)
440
Z1-61
(8602)
Power Loss Restart Delay
Time
Sets the time delay for restart. 10 s
(1 - 300 s)
440
Z1-70
(860B)
Green Contactor Mode Green Contactor Mode opens the output and motor contactors when the bypass unit is idle.
0 : Disabled
1 : Enabled
0
(0, 1)
440
Z1-98
(8627)
Expert
Minimum Drive SW Ver “WARNING: If these parameters are changed, undesired operation of the bypass system
could occur. These parameters should only be changed under guidance of Yaskawa
technical support (1-800-YASKAWA).”
01011
00000 - 65535
441
Z1-99
(8628)
Expert
Maximum Drive SW Ver “WARNING: If these parameters are changed, undesired operation of the bypass system
could occur. These parameters should only be changed under guidance of Yaskawa
technical support (1-800-YASKAWA).”
01011
00000 - 65535
441
◆ Z2: Bypass Control Input/Output
No.
(Hex.)
Name Description
Default
(Range)
Ref.
Z2-01
(8563)
Digital Input 1 Function
(TB2-1)
Sets the function for bypass digital input 1. 21
(0 - 47)
442
Z2-02
(8564)
Digital Input 2 Function
(TB2-2)
Sets the function for bypass digital input 2. 22
(0 - 47)
442
Z2-03
(8565)
Digital Input 3 Function
(TB2-3)
Sets the function for bypass digital input 3. 23
(0 - 47)
442
Z2-04
(8566)
Digital Input 4 Function
(TB2-4)
Sets the function for bypass digital input 4. 24
(0 - 47)
442
Z2-05
(8567)
Digital Input 5 Function
(TB2-5)
Sets the function for bypass digital input 5. 25
(0 - 47)
442
Z2-06
(8568)
Digital Input 6 Function
(TB2-6)
Sets the function for bypass digital input 6. 0
(0 - 47)
442
Z2-07
(8569)
Digital Input 7 Function
(TB2-7)
Sets the function for bypass digital input 7. 0
(0 - 47)
442